HFD LSB 02 §2.7.4 requires an approved HVAC company to full-function test and maintain all fire dampers at least every 4 years, following NFPA 90A and 92A. Electric or pneumatic fire smoke dampers must be maintained, cycled and tested at least every 6 months. Dampers are also visually inspected at least annually (§2.7.3).
Find fire safety service providers in Houston, Texas and compare their bids. Ask providers to document work against the applicable LSB 02 §2.7.4 requirements.
Free to post · No commitment
Damper testing checks that each damper closes fully and latches. Quotes are usually per damper, so include the count and note any dampers that are hard to reach.
Required frequency: Every 4 years; electric or pneumatic fire smoke dampers every 6 months (LSB 02 §2.7.4); annual visual inspection (§2.7.3)
An approved HVAC company (LSB 02 §2.7.4). This is not an SFMO/TDI fire-protection license class; review the company's documentation and insurance on its profile.
At least every 4 years under LSB 02 §2.7.4, and every 6 months for electric or pneumatic fire smoke dampers. Ceiling radiation dampers follow §2.7.5 (at least 10% per floor or fire zone each year).
An approved HVAC company (LSB 02 §2.7.4). This is not an SFMO/TDI fire-protection license class; review the company's documentation and insurance on its profile.
FireMarket does not publish a fixed price for this service. Request a quote; price depends on system size and condition, site access, deficiencies found, parts, after-hours work, and the reports or tags required.
Yes. Ask the contractor to price inspection and testing separately from repair or replacement line items, so you can approve corrective work after seeing the findings.
Create a free owner account, post the job, compare bids, and hire on FireMarket. Bidding is capacity-aware, and time-on-site check-in and check-out can document the visit. Booking is not instant.
Add the system and its last test date to your property's compliance calendar. It calculates the next due date from the cited interval, sends reminders, and keeps the report for your proof packet.
Sources: HFD LSB Standard No. 02, Rev. 05 (eff. 01/01/2024) · Houston Fire Code Chapter 12, §1203. FireMarket does not file or submit records to SFMO, TDI, TCEQ, or the AHJ.
Review the provider's available license, insurance, trade, and service-area evidence before making a selection.
Describe the property, trade, scope, and timing so matched providers can respond with relevant bids.
Keep job records and provider documents together for your own review and follow-up.
Create a free account, post your job, and invite providers to submit comparable quotes.
Get Started Free